Bray
Technical datasheet
Generated 2026-11-20
Series 5C Explosion-Proof Valve Status Monitor
モデル Series 5C Explosion-Proof
Control Accessories
Bray
The Bray Series 5C explosion-proof valve status monitor provides unparalleled protection and reliability in harsh environments, with reliable visual and electrical position indication on any VDI/VDE 3845 compliant.
技術仕様
| Certifications | CE, cULus, ATEX, IECEx, SIL 3 capable |
|---|---|
| Communication Protocols | AS-I, Profibus DP, DeviceNet |
| Enclosure Ratings | IP66/67/68, NEMA 4/4X, UL50E Salt Spray |
| Visual Display | High Visibility Indicator; Beacon Color Options: Red/Yellow (Standard), Red/Green, Black/Yellow, Red/Green Inverse |
| Switch Options | Mechanical: SPDT, DPDT; Proximity: PNP, NPN |
| Switch Quantities | Up to 6 |
| Mounting | VDI/VDE 3845 Compliant (NAMUR) |
| Temperature Range | -13°F to 149°F (-25°C to 65°C) |
| Conduit Ports | 2x ¾” NPT, 1x ½ NPT or 2x M25, 1x M20 |
Product description
The Bray Series 5C explosion-proof valve status monitor provides unparalleled protection and reliability in harsh environments, with reliable visual and electrical position indication on any VDI/VDE 3845 compliant quarter-turn device.
A compact, durable enclosure that maintains lasting performance in severe conditions, with a high-visibility dome indicator for precise valve position feedback.
特長と利点
- A. Enclosure: The compact low profile weatherproof VSM is UL certified NEMA Type 4, 4x and IP66/67/68. Aluminum base and cover for exceptional corrosion, wear and impact resistance.
- B. High Visibility Position Indicator: Visual open and closed indication is provided with an impact resistant dome style indicator. Inverting the open and closed visual output is easily done by rotating the indicator dome 90 degrees. There is no need to remove the switchbox aluminum cover and expose internal wiring of the VSM to change position indication.
- C. Stub Shaft Secondary Seal: Ensures indicator area is separate from the VSM’s internals. Provides a secondary seal to prevent water ingress should the dome or dome seal become compromised due to adverse site conditions.
- D. Captive Cover Bolts: The cover is attached to the base by captive stainless steel bolts placed outside the sealing area.
- E. Washers: Stainless steel corrosion resistant washers provide larger contact surface for the captive bolts to secure the cover to the base.
- F. O-Ring Seal for Watertight Enclosure: The O-ring seal between the cover and base provides a weatherproof seal to prevent water ingress and internal corrosion.
- G. Sensor Cams: Splined cam design allows for easy and accurate setting of switch activation without the use of tools.
- H. Limit Switches: Up to six switch options and configurations to meet connectivity requirements.
- I. Terminals: Clearly marked terminal blocks are angled towards the user to ensure easy access.
- J. Conduit Entries: Three conduit entries available in either imperial or metric threads.
- K. Grounding: Green color-coded, easy-access grounding bolt.
Quotation and documentation
口径・接続方法・使用条件をお知らせください。1営業日以内に価格・納期・添付書類の範囲をご返信します。
22244579@qq.com
+86 138 5000 1310